PDQIE - PDQ Industrial Electric
Arc Fault Flash Analysis
An arc flash (or arc blast) is a type of electrical explosion that results from a low impedance
connection to ground or another voltage phase in an electrical system.
DEFINITION
An arc flash is an electrical breakdown of the resistance of air resulting in an electric arc which
can occur where there is sufficient voltage in an electrical system and a path to ground or lower voltage. An arc
flash with 1000 amperes or more can cause substantial damage, fire or injury. The massive energy released in the
fault rapidly vaporizes the metal conductors involved, blasting molten metal and expanding plasma outward with
extreme force. A typical arc flash incident can be inconsequential but could conceivably easily produce a more
severe explosion (see calculation below). The result of the violent event can cause destruction of equipment
involved, fire, and injury not only to the worker but also to nearby people.
In addition to the explosive blast of such a fault, destruction also arises from the intense
radiant heat produced by the arc. The metal plasma arc produces tremendous amounts of light energy from far
infrared to ultraviolet. Surfaces of nearby people and objects absorb this energy and are instantly heated to
vaporizing temperatures. The effects of this can be seen on adjacent walls and equipment - they are often ablated
and eroded from the radiant effects.
EXAMPLES
In general, arc flash incidents are highly improbable on systems operating at less than 208 volts
phase to phase (120 V to ground) when fed by less than a 125 kVA transformer, as 120 volts does not provide
sufficient energy to cause an arc flash hazard. Most 480 V electrical services have sufficient capacity to cause an
arc flash hazard. Medium-voltage equipment (above 600 V) is higher energy and therefore a higher potential for an
arc flash hazard.
As an example of the energy released in an arc flash incident, consider a single phase-to-phase
fault on a 480 V system with 20,000 amps of fault current. The resulting power is 9.6 MW. If the fault lasts for 10
cycles at 60 Hz, the resulting energy would be 1.6 megajoules. For comparison, TNT releases 2175 J/g or more when
detonated (a conventional value of 4,184 J/g is used for TNT equivalent). Thus, this fault energy is equivalent to
380 grams (approximately 0.8 pounds) of TNT. The character of an arc flash blast is quite different from a chemical
explosion (more heat and light, less mechanical shock), but the resulting devastation is comparable. The rapidly
expanding superheated vapor produced by the arc can cause serious injury or damage, and the intense UV, visible,
and IR light produced by the arc can temporarily and sometimes even permanently blind or cause eye damage to
people.
PROTECTING PERSONNEL
There are many methods of protecting personnel from arc flash hazards. This can include personnel
wearing arc flash personal protective equipment (PPE) or modifying the design and configuration of electrical
equipment. The best way to remove the hazards of an arc flash is to de-energize electrical equipment when
interacting with it, however de-energizing electrical equipment is in and of itself an arc flash hazard. In this
case then one of the newest solutions is to allow the operator to stand far back from the electrical equipment by
operating equipment remotely.
ARC FLASH PROTECTION EQUIPMENT
With recent increased awareness of the dangers of arc flash, there have been many companies that
offer arc flash personal protective equipment (PPE). The materials are tested for their arc rating. The arc rating
is the maximum incident energy resistance demonstrated by a material prior to breakopen or at the onset of a
second-degree skin burn. Arc rating is normally expressed in cal/cm2 (or small calories of heat energy per square
centimeter). The tests for determining arc rating is defined in ASTM F1506 Standard Performance Specification for
Flame Resistant Textile Materials for Wearing Apparel for Use by Electrical Workers Exposed to Momentary Electric
Arc and Related Thermal Hazards.
Selection of appropriate PPE, given a certain task to be performed, is normally handled in one of
two possible ways. The first method is to consult a hazard category classification table, like that found in NFPA
70E. Table 130.7(C)(9)(a) lists a number of typical electrical tasks are various voltage levels and recommends the
category of PPE that should be worn. For example when working on 600 V switchgear and performing a removal of
bolted covers to expose bare, energized parts, the table recommends Category 3 Protective Clothing System. This
Category 3 system corresponds to an ensemble of PPE that together offers protection up to 25 cal/cm2 (105 J/cm2 or
1.05 MJ/m2). The minimum rating of PPE necessary for any category is the maximum available energy for that
category. For example, a Category 3 arc-flash hazard requires PPE rated for no less than 25 cal/cm2 (1.05
MJ/m2).
The second method of selecting PPE is to perform an arc flash hazard calculation to determine the
available incident arc energy. IEEE 1584 provides a guide to perform these calculations given that the bolted fault
current, duration of faults, and other general equipment information is known. Once the incident energy is
calculated the appropriate ensemble of PPE that offers protection greater than the energy available can be
selected.
PPE provides protection after an arc flash incident has occurred and should be viewed as the last
line of protection. Reducing the frequency and severity of incidents should be the first option and this can be
achieved through a complete arc flash hazard assessment and through the application of technology such as high
resistance grounding which has been proven to reduce the frequency and severity of incidents.
REDUCING HAZARD BY DESIGN
Three key factors determine the intensity of an arc flash on personnel. These factors are the
quantity of fault current available in a system, the time fault until an arc flash is cleared, and the distance an
individual is from an arc. Various design and equipment configuration choices can be made to affect these factors
and in turn reduce the arc flash hazard.
FAULT CURRENT
Fault current can be limited by using current limiting devices such as grounding resistors or
fuses. If the fault current is limited to 5 amperes or less, then many ground faults self-extinguish and do not
propagate into phase-to-phase faults.
ARCING TIME
Arcing time can be reduced by temporarily setting upstream protective devices to lower setpoints
during maintenance periods or by employing zone-selective interlocking protection (ZSIP).
Arcing time can significantly be reduced by protection based on detection of arc-flash light.
Optical detection is often combined with overcurrent information. Light and current based protection can be set up
with dedicated arc-flash protective relays or by using normal protective relays equipped with arc-flash option.
The most efficient means to reduce arcing time is to use an arc eliminator that will extinguish the
arc within a few milliseconds.
DISTANCE
The distance from an arc flash source within which an unprotected person has a 50% chance of
receiving a second degree burn is referred to as the "flash protection boundary". Those conducting flash hazard
analyses must consider this boundary, and then must determine what PPE should be worn within the flash protection
boundary. Remote operators or robots can be used to perform activities that are high risk for arc flash incidents,
such as inserting draw-out circuit breakers on a live electrical bus.
Did You Know?
Non-invasive Thermography can be done through an Optical Inspection Window, Infrared Viewing Port,
in an Infrared Transmissive Electric Panel Cover.
Contact PDQ Industrial Electric (877) PDQ-4-FIX to
Schedule Your Arc-Flash Survey
|